Skip to main content

Free calculator

Use this calculator to

  • Size cables, breakers and switchgear by converting a kW load into its current draw
  • Check whether a 7.4 kW or 22 kW EV charger fits the circuits a site already has
  • Compare the current a load pulls on 230 V single-phase versus 400 V three-phase
  • Convert DC loads such as battery systems from kW to amps at the bank voltage

kW to Amps Calculator

Convert real power (kW) to current (A).

kW
V
Result
kW
V
PF
Result
kW
V
PF
Result

Formulas

  • DC: A = (kW × 1000) / V
  • AC Single-Phase: A = (kW × 1000) / (V × PF)
  • AC Three-Phase: A = (kW × 1000) / (V × PF × √3)

Common scenarios

Select one to run it in the calculator above.

For business

Why this matters for businesses

The cable, the breaker, and the protection device that feed any piece of plant are all sized in amps, but the kit is bought and specified in kW. A 22 kW DC rapid EV charger draws roughly 32 amps on a 400 V three-phase supply at unity power factor, and the upstream protection has to allow for inrush, harmonic content, and the diversity of whatever else is on the same distribution board. Get the conversion wrong and the install either nuisance-trips or sits oversized for years.

On commercial sites with multiple chillers, compressors, or banks of chargers, the cumulative current draw at peak is what drives the LV switchgear sizing and the agreed capacity with the network operator. A 250 kW chiller plus a 200 kW heat pump retrofit plus a 150 kW EV charger bank does not need a 600 kW supply if the diversity factor is right, but it certainly will if every load is sized in isolation. The conversion between kW and amps, with the right assumptions about three-phase, power factor, and voltage, is how that diversity calculation gets honest.

Purely Energy supports clients planning electrification projects where the combined load shape determines both the engineering scope and the contract design. The conversation usually starts with the equipment nameplates, ends with a capacity strategy that the DNO accepts, and runs through a half-hourly demand audit in the middle. The free converter here is step one of that workflow. For multi-site operators, the conversion gets repeated across every location in the estate, with the answers feeding the capital plan, the contract renewals calendar, and the SECR reporting line for the year ahead.

Common questions

How do I convert kW to amps?

It depends on the supply. DC: amps = kW x 1,000 / volts. AC single-phase: amps = kW x 1,000 / (volts x PF). AC three-phase: amps = kW x 1,000 / (volts x PF x 1.732), using the 400 V line voltage. Power factor (PF) matters for AC because the current must cover reactive power too: at PF 0.8 a load draws 25 percent more current than the kW alone suggests.

How many amps does a 7.4 kW EV charger draw?

On a 230 V single-phase supply at unity power factor, 7,400 / 230 = 32.2 A, which is why 7.4 kW chargers are installed on dedicated 32 A circuits. A 22 kW three-phase charger draws 22,000 / (400 x 1.732) = 31.8 A per phase, so it also sits on a 32 A way but needs all three phases. Always confirm spare capacity at the distribution board before adding chargers.

Why does three-phase draw less current for the same kW?

A three-phase supply delivers power across three conductors at a 400 V line voltage, so the work is shared. The same 22 kW load draws roughly 96 A on 230 V single-phase but under 32 A per phase on 400 V three-phase at unity power factor. Lower current means smaller cables, lower losses and less voltage drop, which is why motors and larger plant are almost always connected three-phase.

Is the UK mains 230 V or 240 V?

The nominal voltage is 230 V single-phase and 400 V three-phase, harmonised across Europe, with a permitted tolerance of +10 percent to -6 percent. In practice many UK sites measure nearer 240 V because the network was built to the older standard. For cable and breaker sizing, calculating at 230 V is the conservative convention, since lower voltage means higher current for the same kW.

What power factor should I use for the AC calculations?

Resistive loads such as heaters and immersion elements run at 1.0. Motors typically run between 0.8 and 0.9 under load, and lower when lightly loaded. EV chargers and modern IT power supplies operate close to unity. If you have half-hourly metering, divide recorded kW by recorded kVA for the true site figure. When in doubt, 0.9 is a reasonable commercial assumption that slightly overstates current.

kW to Amps Calculator | Free UK Tool | Purely Energy