Skip to main content

Free calculator

Use this calculator to

  • Check whether a rack UPS will overload a 13 A or 16 A circuit before installing it
  • Size cables and breakers for comms cabinets from VA nameplate ratings
  • Work out the line current a 100 kVA transformer draws at 400 V three-phase
  • Compare single-phase and three-phase current for the same VA load using the two tabs

VA to Amps Calculator

Convert apparent power (VA) to current (A).

VA
V
Result
VA
V
Result

Formulas

  • Single-Phase: A = VA / V
  • Three-Phase: A = VA / (V × √3)

Common scenarios

Select one to run it in the calculator above.

For business

Why this matters for businesses

VA to amps is the workhorse conversion for anyone specifying UPS, inverter, transformer or generator equipment on a UK commercial site. Manufacturers rate kit in kVA because the apparent power is what determines the copper, the iron and the cooling. Installers, however, need to know the per-phase amps so they can size cables, breakers and protection. A 100 kVA UPS on a 400 V three-phase supply draws 144 amps per phase at unity power factor, and rather more once the protected load is reactive. Specifying the breaker for the kW figure rather than the kVA figure is a regular cause of nuisance trips on day one.

For comms rooms, manufacturing process islands and any site running a static UPS in double-conversion, the VA to amps maths also dictates how much spare capacity the supply panel actually holds. Adding a second UPS module to a panel that looks fine on a kW spreadsheet routinely overloads the upstream MCCB once the kVA is read against amps. The same applies to inverter sizing on solar and battery projects, where the inverter nameplate is in kVA but the AC-side cable and protection has to be designed against amps. Get the conversion wrong and the bill is a re-pull of cable.

Purely Energy sees the downstream consequences of these decisions on the supplier bill. Sites that consistently run a low power factor pay reactive charges and risk an MIC uplift; sites that run their UPS panels close to nameplate amps tend to also be the sites whose maximum demand spikes hit DUoS red bands. Treating the VA to amps conversion as a routine sanity check on every panel diagram tightens the link between the kit nameplates, the supply capacity, and the monthly invoice. The tool above is for the engineering side; the contract conversation is where we add value.

Common questions

How do I convert VA to amps on a single-phase supply?

Divide the apparent power by the voltage: A = VA / V. On a UK 230 V single-phase supply, a 1,500 VA UPS draws 1,500 / 230 = 6.5 A. This is the current the cable, plug and breaker must carry, so it is the figure to check against a 13 A plug or a 16 A radial circuit.

How do I convert VA to amps on a three-phase supply?

Use the line voltage and the square root of 3: A = VA / (V x 1.732). For a 10,000 VA (10 kVA) three-phase UPS on a UK 400 V supply, the current per phase is 10,000 / (400 x 1.732) = 14.4 A. Always use the 400 V line voltage in this formula, not the 230 V phase-to-neutral figure.

Why are UPS systems rated in VA rather than watts?

VA measures apparent power, the product of voltage and current, which is what the UPS inverter and transformer must physically carry. Watts measure the real power the load consumes, and the two differ by the power factor (W = VA x power factor). A UPS therefore carries two limits, a VA limit and a watt limit, and the connected load must sit inside both.

What current does a 3,000 VA UPS draw at 230 V?

3,000 / 230 = 13.0 A at full load, which sits right at the limit of a 13 A plug. In practice a UPS of this size should go on a dedicated 16 A circuit, both for the running current and for the battery recharge load after an outage. Use the single-phase tab with your own figures to check the headroom.

Is VA the same as watts?

No. VA is apparent power and watts are real power; they are equal only when the power factor is exactly 1. IT loads with power-factor-corrected supplies run close to unity, but mixed loads with motors or older equipment can sit nearer 0.8, where a 1,000 VA load delivers only 800 W of useful power. For sizing current, cables and breakers, VA is the figure that matters.

VA to Amps Calculator | Purely Energy